ABB
1SDA054698R1PR222DS/P-LSIG In=400 T5 3p
PR222DS/P-LSIG In=400 T5 3p
Trip unit alone - ABB / SACE (Tmax T (IEC) series) - PR222DS/P-LSIG In=400 T5 3p - 3-poles (3P3d) - Rated current 400A - Electronic (PR222DS/P-LSIG) trip unit - equivalent to PR222DSPLSIGIn400T53p
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
1SDA054698R1
Please add this item to cart to request a quote.
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
1SDA054698R1ABB - Tmax T accessories 2006
Description
Trip unit alone - ABB / SACE (Tmax T (IEC) series) - PR222DS/P-LSIG In=400 T5 3p - 3-poles (3P3d) - Rated current 400A - Electronic (PR222DS/P-LSIG) trip unit - equivalent to PR222DSPLSIGIn400T53p
Specifications
Primary brand
ABB
Secondary brand
SACE
Main function
Trip unit
Product series / family name
Tmax T (IEC)
Sub-range name
T5 trip units alone
Functions
Trip unit alone
Protection parameters set (available via Modbus)
Protections (L/S/I/G) (available via Modbus)
Failed tripping under fault conditions (available via Modbus)
Protection parameters set (available via Modbus)
Protections (L/S/I/G) (available via Modbus)
Failed tripping under fault conditions (available via Modbus)
Poles
3-poles (3P3d)
Rated current
400A
Trip current rating
400 AT
Trip unit type
Electronic
PR222DS/P-LSIG
LSIG
Display = none
PR222DS/P-LSIG
LSIG
Display = none
Protection functions
(L) Protection against overload
(S) Protection against short-circuit with time delay
(I) Instantaneous protection against short-circuit
(G) Protection against earth fault
(S) Protection against short-circuit with time delay
(I) Instantaneous protection against short-circuit
(G) Protection against earth fault
Protection settings
L - Protection against overload -- adjustable 0.4...1 x In (160A...400A)
S - Protection against short-circuit with time delay -- adjustable 0.6...10 x In (240A...4000A); with adjustable time trip curve
I - Instantaneous protection against short-circuit -- adjustable 1.5...12 x In (600A...4800A)
G - Protection against earth fault -- adjustable 0.2...1 x In (0.1...0.8s time delay)
S - Protection against short-circuit with time delay -- adjustable 0.6...10 x In (240A...4000A); with adjustable time trip curve
I - Instantaneous protection against short-circuit -- adjustable 1.5...12 x In (600A...4800A)
G - Protection against earth fault -- adjustable 0.2...1 x In (0.1...0.8s time delay)
Measurement function
Phase currents
Ground current
Ground current
Order code / Manufacturer SKU
PR222DS/P-LSIG In=400 T5 3p
Manufacturer product status
Commercialized
Equivalent to
PR222DSPLSIGIn400T53p
EAN code
8015644558123
Related Documents
Name | Last Update | Language |
---|---|---|
ABB - Tmax T Moulded Case Circuit Breakers - Catalogue (2006).pdf | 02 Feb 2023 | English (US) |